Influence of Measurement Uncertainty of Power Quality Instruments on Harmonic State Estimation

Research output: Contribution to book/Conference proceedings/Anthology/ReportConference contributionContributedpeer-review

Contributors

Abstract

Harmonic State Estimation (HSE) integrates measurements and simulations to fully determine the voltages and current harmonics of the network. However, the measurement uncertainty may affect significantly the results of the HSE. This paper analyses the influence of the typical uncertainty of PQ instruments on the results of HSE for transmission networks. The results show that PQ instruments according to IEC 61000-4-30 class A which can measure the harmonic phase angles referred to an absolute time reference, provide accurate HSE results for those harmonic orders with relevant disturbance levels.

Details

Original languageEnglish
Title of host publication2024 IEEE 14th International Workshop on Applied Measurements for Power Systems (AMPS)
Number of pages6
ISBN (electronic)979-8-3503-7531-2
Publication statusPublished - 2024
Peer-reviewedYes

Publication series

SeriesIEEE International Workshop on Applied Measurements for Power Systems (AMPS)
ISSN2473-1315

External IDs

Scopus 85207849526
ORCID /0000-0002-7465-5750/work/192578706

Keywords

Keywords

  • harmonic distortion, harmonic state estimation, uncertainty measurements