Impact of Aggregation Interval on Harmonic Phase Angle Measurements

Research output: Contribution to book/Conference proceedings/Anthology/ReportConference contributionContributedpeer-review

Contributors

Abstract

The aggregation principles of IEC 61000-4-30 is a well-known concept implemented in Power Quality (PQ) recorders. Only rms data is retained. Harmonic emission assessment requires the analysis of harmonic phasors. Continuous measurement of harmonic phasors is constrained by the volume of data resulting if the measurement period is longer. An innovative approach to also aggregate harmonic phase angles has been introduced and this paper evaluates how the aggregation interval affect the application of this concept in harmonic emission. Two different types of harmonic emission sources are evaluated in a distribution network. Results from this field data are used to demonstrate that although it is not possible to use a standard aggregation interval as in the IEC 61000-4-30, that the concept of aggregating harmonic phasors present an improved understanding of harmonic emission.

Details

Original languageEnglish
Title of host publication2018 IEEE 9th International Workshop on Applied Measurements for Power Systems (AMPS)
PublisherIEEE
Pages1-6
Number of pages6
ISBN (electronic)978-1-5386-5375-3
ISBN (print)978-1-5386-5376-0
Publication statusPublished - 28 Sept 2018
Peer-reviewedYes

Publication series

SeriesIEEE International Workshop on Applied Measurements for Power Systems (AMPS)
ISSN2473-1315

Conference

Title2018 IEEE 9th International Workshop on Applied Measurements for Power Systems (AMPS)
Duration26 - 28 September 2018
LocationBologna, Italy

External IDs

Scopus 85057370618
ORCID /0000-0002-7465-5750/work/142237852

Keywords

Keywords

  • Harmonic analysis, Current measurement, Power system harmonics, IEC Standards, Phase measurement, Voltage measurement