Impact of Aggregation Interval on Harmonic Phase Angle Measurements
Research output: Contribution to book/Conference proceedings/Anthology/Report › Conference contribution › Contributed › peer-review
Contributors
Abstract
The aggregation principles of IEC 61000-4-30 is a well-known concept implemented in Power Quality (PQ) recorders. Only rms data is retained. Harmonic emission assessment requires the analysis of harmonic phasors. Continuous measurement of harmonic phasors is constrained by the volume of data resulting if the measurement period is longer. An innovative approach to also aggregate harmonic phase angles has been introduced and this paper evaluates how the aggregation interval affect the application of this concept in harmonic emission. Two different types of harmonic emission sources are evaluated in a distribution network. Results from this field data are used to demonstrate that although it is not possible to use a standard aggregation interval as in the IEC 61000-4-30, that the concept of aggregating harmonic phasors present an improved understanding of harmonic emission.
Details
Original language | English |
---|---|
Title of host publication | 2018 IEEE 9th International Workshop on Applied Measurements for Power Systems (AMPS) |
Publisher | IEEE |
Pages | 1-6 |
Number of pages | 6 |
ISBN (electronic) | 978-1-5386-5375-3 |
ISBN (print) | 978-1-5386-5376-0 |
Publication status | Published - 28 Sept 2018 |
Peer-reviewed | Yes |
Publication series
Series | IEEE International Workshop on Applied Measurements for Power Systems (AMPS) |
---|---|
ISSN | 2473-1315 |
Conference
Title | 2018 IEEE 9th International Workshop on Applied Measurements for Power Systems (AMPS) |
---|---|
Duration | 26 - 28 September 2018 |
Location | Bologna, Italy |
External IDs
Scopus | 85057370618 |
---|---|
ORCID | /0000-0002-7465-5750/work/142237852 |
Keywords
Keywords
- Harmonic analysis, Current measurement, Power system harmonics, IEC Standards, Phase measurement, Voltage measurement