Influencing factors on field distribution of GIS insulators under DC voltage

Research output: Contribution to book/conference proceedings/anthology/reportConference contributionContributedpeer-review

Contributors

  • Shiliang Zhao - , Technical University of Munich (Author)
  • Josef Kindersberger - , Technical University of Munich (Author)
  • Maria Hering - , Siemens AG (Author)
  • Karsten Juhre - , Siemens AG (Author)

Abstract

In order to understand the gas-solid insulation system under DC voltage, a simulation model is developed to determine the electric field distribution in such systems. Various influencing factors are integrated in the simulation model, including the temperature and field-dependent volume und surface conductivity, the shape of the insulator, the polarisation and the dark current. The effects of the influencing factors are investigated individually. The combination of the influencing factors that results in the highest field strength in the gas-solid insulation systems is determined, which gives a worst-case scenario.

Details

Original languageEnglish
Title of host publicationVDE Hochspannungstechnik 2018, ETG-Fachbericht
PublisherVDE Verlag, Berlin [u. a.]
Pages445-450
Number of pages6
ISBN (print)978-3-8007-4807-5
Publication statusPublished - 14 Nov 2018
Peer-reviewedYes
Externally publishedYes

Conference

TitleVDE Hochspannungstechnik 2018
Conference number
Duration12 - 14 November 2018
Degree of recognitionNational event
LocationBerlin
City

External IDs

ORCID /0000-0002-4114-388X/work/165453907
Scopus 85096798333