Harmonic and supraharmonic disturbances caused by the combined operation of fast charging stations and a battery storage

Research output: Contribution to book/Conference proceedings/Anthology/ReportConference contributionContributedpeer-review

Abstract

This paper presents a field study, in which three battery-electric vehicles were connected one after the other to a fast charging installation in a public low voltage network. The installation includes also a battery energy storage system for peak shaving purposes. One aspect of the field test was an assessment of the impact of the fast charging installation on power quality parameters such as the harmonic and supraharmonic distortion. This paper discusses both the current emission and the respective impact on the voltage disturbance levels in the network. Furthermore, the summation of harmonics is studied and the impact on voltage disturbance levels at the point of connection are compared with those at the transformer busbar, which is the point of common coupling.

Details

Original languageEnglish
Title of host publicationCIRED Porto Workshop 2022: E-mobility and power distribution systems
Number of pages5
Publication statusPublished - Jun 2022
Peer-reviewedYes

External IDs

Mendeley af56a301-184f-32d4-8b5f-94e27e75ad2b
unpaywall 10.1049/icp.2022.0869
Scopus 85174646984

Keywords