Abstract

The correct transposition of overhead lines is crucial for optimal operation. Often, the conductor sequence is determined in a late planning step. In this case, there is a risk that the transposition is not designed in an optimal way. Unfavorably transposed lines lead, for example, to unbalanced currents and voltages at the points of common coupling and therefore to increased field strengths in the direct area of the line. This paper shows how the transposition should be designed in order to ensure symmetry of the line. It also includes a discussion of the formation of the cou-pling matrices and an advanced, detailed representation of the unbalance, which allows for a more comprehensive analysis of the system behavior. The effects of unfavorably transposed overhead lines are presented taking into account the electrical unbalance. Conventional transposition variants are compared and it is shown that a one-third separation of the line length does not automatically lead to a symmetrical line. The unbalance is calcu-lated as a function of the conductor sequence at the beginning of the line, depending on the load, and is compared and evaluated for correctly and unfavorably designed transposition. As a result, it is shown that transposition variations exist which can produce symmetrical operating lines independently of load situation.

Details

Original languageEnglish
Pages82 - 87
Number of pages6
Publication statusPublished - 21 Jun 2024
Peer-reviewedYes

Conference

TitleIEEE Power and Energy Student Summit 2023
Abbreviated titlePESS 2023
Duration15 - 17 November 2023
Website
Degree of recognitionNational event
LocationHochschule Bielefeld
CityBielefeld
CountryGermany

External IDs

ORCID /0000-0001-8439-7786/work/162347938
ORCID /0009-0002-2649-8903/work/165877596

Keywords

Keywords

  • overhead line, impedance, transposition, unbalance