Partial Discharge Behaviour in Gas-Insulated Systems with Fluoronitriles: Measurement of the UHF Spectra
Publikation: Beitrag in Buch/Konferenzbericht/Sammelband/Gutachten › Beitrag in Konferenzband › Beigetragen › Begutachtung
Beitragende
Abstract
In the last decade alternative insulating gases for gas-insulated systems (GIS) have been established on the market to lower the global warming potential of the electrical energy network. Partial discharge (PD) measurements are a typical diagnosis instrument to identify typical defects in GIS. One specific PD measurement method is measuring the frequency spectrum of the PDs in the ultra-high frequency (UHF) range using a spectrum analyser. This contribution presents UHF spectra measured in a fluoronitrile mixture as well as in carbon dioxide. Two typical defects were investigated: fixed protrusion on ground potential and free-moving particle. The results indicate that defect recognition is possible evaluating exclusively the UHF spectrum. A comparison with literature sources suggests similar UHF spectra for the analysed alternative insulating gases and sulphur hexafluoride when looking at the same defects.
Details
| Originalsprache | Englisch |
|---|---|
| Titel | VDE Hochspannungstechnik 2024 : 5. ETG-Fachtagung, 11.-13. November 2024 in Berlin / VDE ETG |
| Erscheinungsort | Berlin |
| Herausgeber (Verlag) | VDE Verlag, Berlin [u. a.] |
| Seiten | 205-2012 |
| Seitenumfang | 8 |
| Band | 175 |
| ISBN (elektronisch) | 978-3-8007-6467-9 |
| Publikationsstatus | Veröffentlicht - Nov. 2024 |
| Peer-Review-Status | Ja |