Novel Harmonic Emission Limit Concept for Series-connected Distorting Installations Connected to Transmission Systems

Publikation: Beitrag in Buch/Konferenzbericht/Sammelband/GutachtenBeitrag in KonferenzbandBeigetragenBegutachtung

Beitragende

Abstract

The current technical standards for allocating harmonic emission limits in transmission systems do not consider series-connected distorting installations (like TCSC, HVDC links, etc.). This paper introduces a novel approach for the calculation of harmonic emission limits for series elements. The approach is developed based on the results of simulations of a test network with TCSCs connected in different lines, which showed that TCSCs have a considerable effect on the harmonic emission, and therefore series elements should be considered in the allocation process. Different global and local approaches for the harmonic emission limits allocation are proposed and applied exemplarily to the considered test network.

Details

OriginalspracheEnglisch
Titel2024 21st International Conference on Harmonics and Quality of Power (ICHQP)
Redakteure/-innenXianyong Xiao, Yang Wang
Seiten479-484
Seitenumfang6
ISBN (elektronisch)979-8-3503-8256-3
PublikationsstatusVeröffentlicht - 17 Okt. 2024
Peer-Review-StatusJa

Externe IDs

Scopus 85213390284
ORCID /0000-0002-7465-5750/work/192578705

Schlagworte

Schlagwörter

  • harmonic allocation, transmission system, harmonic emission limits, series connected distorting installation