Influence of zero-sequence impedance inaccuracy on the detection of phase-to-ground faults by distance protection relays

Publikation: Beitrag zu KonferenzenPaperBeigetragenBegutachtung

Abstract

Phase-to-ground faults are the most common type of fault on overhead lines and require accurate detection and selective isolation by distance protection systems to ensure reliable energy transmission. Conventional distance protection relays analyse the impedance of the phase-ground loop of the affected phase, utilizing line impedances to configure relays settings specific to each line. Accurate setting parameters are among the most critical components in a distance protection relay, as they are essential for determining the correct fault distance. Inaccurate settings can significantly reduce the accuracy of the protection system. These settings include the symmetrical components of positive-sequence and zero-sequence impedances, along with the resulting ground current compensation factor, so-called kE-factor.
Building on a previously developed line model that realistically simulates overhead lines —including finite length of ground wires and resistances of the tower grounding system — this paper explores the sensitivity of the zero-sequence impedance and the ground current compensation factor in distance protection relays by analysing the impact of variations in influencing variables. A case study illustrates discrepancies between calculated and measured impedances in real overhead lines. Further, potential errors in impedance determination, such as inaccuracies from oversimplified mathematical models, are also addressed, highlighting the influencing variables that affect zero-sequence impedance and kE-factor
Titel in Übersetzung
Einfluss der Ungenauigkeit der Nullimpedanz auf die Erkennung von Phase-Erde-Fehlern durch Distanzschutzrelais

Details

OriginalspracheEnglisch
Seiten105-109
Seitenumfang5
PublikationsstatusVeröffentlicht - 1 Apr. 2025
Peer-Review-StatusJa

Konferenz

Titel19th IET Conference on Developments in Power System Protection
KurztitelDPSP Europe 2025
Veranstaltungsnummer19
Dauer1 - 3 April 2025
Webseite
BekanntheitsgradInternationale Veranstaltung
OrtBizkaia Aretoa
StadtBilbao
LandSpanien

Externe IDs

ORCID /0009-0002-2649-8903/work/184004985
ORCID /0000-0001-8439-7786/work/184005470
unpaywall 10.1049/icp.2025.1053
Scopus 105007000711

Schlagworte

ASJC Scopus Sachgebiete

Schlagwörter

  • distance protection, line protection, phase-ground-fault, ground current compensation factor, impedance calculation, CONDUCTOR-GROUND LOOP, DISTANCE PROTECTION, GROUND IMPEDANCE COMPENSATION FACTOR, IMPEDANCE CALCULATION, LINE PROTECTION