Influence of Test Signal Parameters on the Frequency Response Measurement of Current Transformers
Publikation: Beitrag in Buch/Konferenzbericht/Sammelband/Gutachten › Beitrag in Konferenzband › Beigetragen › Begutachtung
Beitragende
Abstract
The growing presence of power electronic converters has introduced new challenges for power quality, particularly due to distortion at frequencies above 2 kHz. To address this issue, the definition of accuracy classes for instrument transformers has been extended to include frequencies beyond the fundamental (wideband classes). However, simple and credible methodology for characterizing the ratio error and phase displacement of instrument transformers is still under development. This paper focuses on current transformers and presents a test setup developed to identify their frequency response characteristics. Using this setup, the frequency response of six conventional current transformers was measured up to 20 kHz, corresponding to wideband class WB2. In addition, the influence of key test signal parameters, such as current magnitudes and the number of distortion components, was evaluated. The results reveal significant differences between current transformers with turn ratios below and above 100, with the latter showing indications of resonance behavior. In contrast, the influence of fundamental current magnitude remains negligible up to 20 kHz.
Details
| Originalsprache | Englisch |
|---|---|
| Titel | 2025 IEEE 15th International Workshop on Applied Measurements for Power Systems (AMPS) |
| Herausgeber (Verlag) | IEEE Canada |
| Seiten | 1-6 |
| Seitenumfang | 6 |
| ISBN (Print) | 978-1-6654-7766-6 |
| Publikationsstatus | Veröffentlicht - 26 Sept. 2025 |
| Peer-Review-Status | Ja |
Workshop
| Titel | 15th IEEE International Workshop on Applied Measurements for Power Systems |
|---|---|
| Kurztitel | AMPS 2025 |
| Veranstaltungsnummer | 15 |
| Dauer | 24 - 26 September 2025 |
| Webseite | |
| Ort | Politehnica University of Bucharest |
| Stadt | Bucharest |
| Land | Rumänien |
Externe IDs
| ORCID | /0000-0001-6072-4500/work/196669730 |
|---|---|
| ORCID | /0000-0003-1882-3155/work/196675116 |
| ORCID | /0000-0002-9052-3838/work/196679779 |
Schlagworte
Schlagwörter
- Accuracy, Uncertainty, Power measurement, Current transformers, Current measurement, Resonant frequency, Frequency response, Resonance, Frequency measurement, Wideband