A photovoltaic inverter (PVI) may enter operational instability region based on grid supply conditions, such as the presence of voltage waveform distortions and high grid impedance, especially when the actual power output of the PVI is low. This paper considers evaluation and modelling of one commercially available 3-phase PVI, for which laboratory tests showed instability when it was operating with a low power output and connected to a distorted voltage supply. A full switching model of the considered PVI is developed using simulated and measured frequency-based impedance plots, which are also used to calculate approximate values of the PVI output filter, as well as the type and parameters of its control. Afterwards, the operational stability of the PVI is evaluated using impedance-based and Nyquist stability criteria.

Details

OriginalspracheEnglisch
TitelICHQP 2022 - 2022 20th International Conference on Harmonics and Quality of Power
Herausgeber (Verlag)IEEE Computer Society
ISBN (elektronisch)9781665416399
PublikationsstatusVeröffentlicht - 2022
Peer-Review-StatusJa

Publikationsreihe

ReiheProceedings of International Conference on Harmonics and Quality of Power, ICHQP
Band2022-May
ISSN1540-6008

Konferenz

Titel20th International Conference on Harmonics and Quality of Power, ICHQP 2022
Dauer29 Mai - 1 Juni 2022
StadtNaples
LandItalien

Externe IDs

ORCID /0000-0001-5338-7649/work/165878471
ORCID /0000-0002-1779-2281/work/165878766

Schlagworte

Ziele für nachhaltige Entwicklung

Schlagwörter

  • Distorted grid, filter, grid-connected inverter, impedance-based model, parameter identification, photovoltaic inverter, stability analysis